- Overview Features
- Included Items
- Tech Specs
Model 6220F – Double Hi-Power Enclosure Integrity Testing
The Model 6220F is a high-power, dual-fan system designed for large-scale enclosure integrity testing. It consists of two complete 6110F systems that can be used independently or combined with the Leakage Split Kit for ceiling neutralization, providing unmatched versatility.
Equipped with two 1 hp calibrated fans, this system is ideal for testing large enclosures up to 102,000 cubic feet (2,900 m³) for Inert agents and 212,000 cubic feet (6,000 m³) for halocarbon agents. It includes fan cases, tool cases, and the newly released, industry-changing DM32X gauge for precision and real-time data collection.
The double high-power fans offer a significant advantage—not only in testing enclosures of virtually any size but also in evaluating large dampers while installed. This system ensures the ability of high-power fans to open the dampers and accurately measure the entire relief vent pathway, confirming peak pressure specifications are not exceeded.
This system supports hold time testing in flooded volumes up to 102,000 cubic feet (2,900 m³) for Inert agents and 140,000 cubic feet (4,000 m³) for halocarbon agents. It also enables venting tests for volumes up to 24,000 cubic feet (660 m³) for Inert agents and can individually measure vents up to 16 square feet (1.6 m²).
Why Choose Retrotec for Enclosure Integrity Testing?
Retrotec pioneered the concept of Enclosure Integrity testing in 1984 and has remained the industry leader ever since. By promoting it within NFPA and authoring the first Enclosure Integrity standard in 1986, Retrotec set the foundation for modern testing methods. As the leading researcher in enclosure testing, Retrotec provides unparalleled expertise, with every major clean agent system manufacturer worldwide relying on its technology for hold time and peak pressure predictions. All Retrotec systems come with expert technical support, ensuring professionals have the guidance they need for accurate and efficient testing.
2 x 6000 Series Fan Set
- 6000 Series Calibrated Fan
(120V/60Hz, 240V/50Hz, or 110V/50Hz) - Range Ring A
- B8 Plate
- 8 x Blank Range Plugs
- Blower Door Tubing Kit
- Tubing Umbilical
- Fan Cover
- Power Cord
- System Calibration Verification Report
1 x Large Cloth Door Panel & Frame Package – Double Fan
- Double-Hole SmartCloth™ Wind Dampening Cloth Door
- Large SmartCloth™ Wind Dampening Cloth Door
- Large Aluminum Frame, Etched with Sizing Markings
- Traveling Case
1 x Leakage Split Kit
- Flex Duct
- Flex Duct Fill-In Sheet
- Subfloor test panel
- Field Calibration Plate for Modular Panel
- Flex Duct Case with Shoulder Strap
2 x DM32X Gauge Package
- DM32X Gauge
- Gauge Case
- USB-C Charging Cable
- Cat5 Cable
- ISO17025 calibration of DM32X
- Gauge Calibration Verification Report
2 x System Accessories Case
2 x Fan Case
8 x Roll of Grill Masks
Model 6000 Fan | ||||
Flow Into: | CFM | Litres/sec | M3/h | |
Max Flow, per fan (60 Hz)
Reduces values by 15% for 50Hz fan |
Free Air | 8,100 | 3,823 | 13,762 |
50 Pa | 7,700 | 3,634 | 13,082 | |
75 Pa | 7,400 | 3,492 | 12,573 | |
Minimum Flow: | ||||
on Included Range B1 | 50 Pa | 95 | 49 | 161 |
on Optional Range 74 | 50 Pa | 37 | 17 | 63 |
on Optional Range 47 | 50 Pa | 21 | 10 | 35 |
on Optional Range 29 | 50 Pa | 9 | 4 | 15 |
Dimensions: | 22″ (55.9 cm) inlet diameter, 9.75″ (24.8 cm) long, 25″ (63.5 cm) height | |||
Weight: | 33.5 lb (15.2 kg) or 35.2 lb (16.0 kg) with Ring A & Plated B8 installed | |||
Flow Accuracy: | +/-5% | |||
Power: | 120V@60hz/22.0A or 240V@50hz/10.9A or 110V@50Hz/22.0A | |||
Recommended Fan Calibration Interval: | 5 years |