- Overview Features
- Included Items
- Tech Specs
Model 5120F with Hard Panel
The Model 5120F with Hard Panel delivers the same reliable performance as the Model 5100F cloth panel system but includes modular hard panels for a quick setup and a professional appearance. Designed for efficiency and durability, this system enhances testing operations with a sturdy and adaptable framework.
This package includes a fan case, tool case, and a large aluminum frame with a cloth panel, ensuring secure setups in tight enclosures. It also features the newly released, industry-changing DM32X gauge, providing precision and ease of use for enclosure integrity testing.
Why Choose Retrotec for Enclosure Integrity Testing?
Retrotec pioneered the concept of Enclosure Integrity testing in 1984 and has remained the industry leader ever since. By promoting it within NFPA and authoring the first Enclosure Integrity standard in 1986, Retrotec set the foundation for modern testing methods. As the leading researcher in enclosure testing, Retrotec provides unparalleled expertise, with every major clean agent system manufacturer worldwide relying on its technology for hold time and peak pressure predictions. All Retrotec systems come with expert technical support, ensuring professionals have the guidance they need for accurate and efficient testing.
1 x 5000 Series Fan Set
- 5000 Series Calibrated Fan
(120V/60Hz, 240V/50Hz, or 110V/50Hz) - Range Ring A
- B8 Plate
- 8 x Blank Range Plugs
- Blower Door Tubing Kit
- Tubing Umbilical
- Fan Cover
- Power Cord
- System Calibration Verification Report
1 x Hard Panel Set
1 x Large SmartCloth™ Door Panel & Frame
- Large SmartCloth™ Wind Dampening Cloth Door
- Large Aluminum Frame, Etched with Sizing Markings
- Traveling Case
1 x DM32X Gauge Package
- DM32X Gauge
- Gauge Case
- USB-C Charging Cable
- Cat5 Cable
- ISO17025 calibration of DM32X
- Gauge Calibration Verification Report
1 x System Accessories Case
1 x Fan Case
4 x Roll of Grill Masks
Model 5000 Fan | ||||
Flow Into: | CFM | Litres/sec | M3/h | |
Max Flow, per fan (60 Hz)
Reduces values by 15% for 50Hz fan |
Free Air | 6,400 | 3,020 | 10,874 |
50 Pa | 5,700 | 2,690 | 9,684 | |
75 Pa | 5,400 | 2,549 | 9,175 | |
Minimum Flow: | ||||
on Included Range B1 | 50 Pa | 111 | 52 | 188 |
on Optional Range 74 | 50 Pa | 37 | 17 | 63 |
on Optional Range 47 | 50 Pa | 21 | 10 | 35 |
on Optional Range 29 | 50 Pa | 9 | 4 | 15 |
Dimensions: | 22″ (55.9 cm) inlet diameter, 9.75″ (24.8 cm) long, 25″ (63.5 cm) height | |||
Weight: | 33.5 lb (15.2 kg) or 35.2 lb (16.0 kg) with Ring A & Plated B8 installed | |||
Flow Accuracy: | +/-5% | |||
Power: | 120V@60hz/11A or 240V@50hz/4.9A or 110V@50Hz/ 8.9A | |||
Recommended Fan Calibration Interval: | 5 years |